Voltage Drop Calculator
Calculate electrical voltage drop instantly using wire size, current, distance, voltage, phase type, conductor material, and NEC standards.
Circuit Inputs
Use NEC Chapter 9 reference values for wire resistance and reactance. The most common workflow for sizing real-world feeder and branch circuits.
Real-world templates
What Is Voltage Drop?
Voltage drop is the reduction in electrical potential as current flows through a conductor. Every wire has some resistance (and AC wires also carry reactance), so the voltage you measure at the load is always lower than the voltage delivered from the source. The longer the run, the smaller the wire, and the larger the current, the bigger the drop. Excessive voltage drop wastes energy, weakens equipment, dims lighting, and can prematurely fail motors.
This calculator uses NEC Chapter 9 reference data to compute drop for DC, single-phase, and three-phase circuits. You can also estimate resistance from first principles, enter custom impedance values from a datasheet, or have the recommender pick the smallest wire size that meets both your voltage-drop and ampacity targets — useful tools for any engineer, electrician, solar installer, or DIY-er. Pair it with our unit converter when working in metric, or our scientific calculator for related electrical math.
How Voltage Drop Works
Ohm's Law in long wires
Voltage drop = I × R for each foot of wire. Multiply by the round-trip path length (2× for DC and single-phase, √3 for three-phase) and you have the total drop seen at the load.
AC adds reactance
On AC circuits, conductor reactance (X) also stores and releases energy each cycle. The effective voltage drop becomes I × (R × PF + X × sin θ) — power factor and the type of conduit (magnetic vs not) both matter.
Temperature increases R
Hotter wire = higher resistance. Resistance scales by roughly 0.39% per °C for copper and 0.40% per °C for aluminum above 20°C — substantial across the 60°C–90°C operating range for THWN insulation.
Size dominates everything
Doubling the cross-sectional area halves resistance. That's why upsizing from 12 AWG to 10 AWG (a ~60% area increase) is the most cost-effective way to cut voltage drop on a long run.
Core Voltage Drop Formulas
Every result this calculator produces comes from one of three closed-form equations. R is the one-way conductor resistance, X is the reactance, I is the load current, and PF is the power factor (≤ 1.0). sin θ is automatically derived as √(1 − PF²).
DC
V_drop = 2 × I × R
Round-trip resistance × current. No reactance, no phase factor — pure Ohm's Law.
AC Single Phase
V_drop = 2 × I × (R · PF + X · sin θ)
Adds the reactive term. Conduit type changes X (steel raises it; PVC lowers it).
AC Three Phase
V_drop = √3 × I × (R · PF + X · sin θ)
Three balanced legs share the load; the √3 factor produces ~13% less drop than equivalent single-phase.
How to Use This Calculator
- 1
Pick a calculation mode
Default to NEC Data for everyday wiring. Use Estimated Resistance to model unusual temperatures or non-standard conductors, Custom Resistance for manufacturer-supplied values, and Wire Size Recommendation when you want the smallest legal gauge.
- 2
Enter circuit basics
Choose wire material (copper or aluminum), AWG size, conduit type, and phase. Then fill in source voltage, load current, and one-way distance. The unit toggle handles metric.
- 3
Set power factor if AC
Most resistive loads (heaters, incandescent lighting) run at PF = 1.0. Motors and electronics typically run 0.8–0.95. Lower PF means proportionally more drop on the reactive term.
- 4
Open Advanced for fine control
Add parallel conductors for high-current feeders, change conductor temperature, override the conductor area or resistivity for non-standard cable, or paste in manufacturer R and X figures.
- 5
Calculate and review
Read the drop in volts and percent, check NEC compliance, scan the distance and wire-size charts, and use the report export to keep a clean PDF for your panel schedule.
Key Electrical Concepts
Electrical resistance
Resistance opposes current flow and dissipates energy as heat. Copper has roughly 1.7× the conductivity of aluminum, which is why copper conductors deliver the same current at smaller diameters and lower drop.
Reactance
Reactance is the AC-specific component of opposition caused by the conductor's inductance. In magnetic conduit (steel) X is higher than in PVC, which is why NEC Table 9 reports different values per conduit type.
Impedance |Z|
Impedance is the vector sum of resistance and reactance: |Z| = √(R² + X²). For most cable runs at 60 Hz, R dominates — but for very high currents or long runs, the X contribution is non-trivial.
Power factor
Power factor is the cosine of the angle between current and voltage on an AC circuit. A PF of 1.0 means current and voltage are aligned (resistive load). Lower PF increases the reactive part of voltage drop.
NEC voltage drop
NEC 210.19(A) Informational Note 4 and 215.2(A) Informational Note 2 recommend voltage drop of 3% or less on the branch, 5% combined on feeder + branch. They are guidelines, not hard rules — but inspectors and engineers treat them as a working ceiling.
Ampacity
Ampacity is the maximum continuous current a conductor can carry without exceeding insulation temperature. NEC Table 310.16 lists ampacity by AWG, temperature rating, and conductor count. Always check both voltage drop AND ampacity.
Voltage Drop in Real-World Wiring
Home wiring
Standard 120/240 V residential branch circuits should stay under 3%. 12 AWG copper is fine for 20 A within 50 ft; longer runs (kitchen islands, detached garages) often need 10 AWG or paralleled conductors.
Solar PV systems
PV strings often run on long DC cables before reaching the inverter — every percent of voltage drop is direct yield lost. NEC 690.45 (and most installer guides) recommend ≤ 2% drop from array to inverter, ≤ 3% from inverter to point of interconnection.
RV electrical
RV 12 V DC systems are the worst-case scenario — low voltage, high current, long runs. Even small drops are huge in percent. Most RV electricians upsize wires one or two AWG sizes beyond the ampacity minimum.
Industrial motors
Motors require >95% of nameplate voltage to start under load. NEMA MG 1 allows operation at 90–110% of rated voltage, but starting torque drops with the square of voltage — under-sized feeders are the #1 cause of repeated motor failures.
Battery banks
Inverter-to-battery cables run hundreds of amps over a few feet. Even at 24 or 48 V DC, voltage drop in the battery cabling can starve the inverter under surge loads — 2/0 or larger is standard for serious off-grid installs.
EV chargers
Level-2 chargers pull 40–80 A continuously. Long runs from panel to garage can easily push beyond 3% on undersized wire. Most installers default to 6 AWG copper for 48 A circuits unless the run is exceptionally short.
Underground runs
Direct-burial or PVC conduit runs to outbuildings, well pumps, or yard panels are often 100–300 ft. Aluminum 2 AWG and 4 AWG are common because cost-per-foot drops fast at large diameters — but the metal needs upsizing vs copper.
Generator feeders
Standby generator feeders are sized for full nameplate current with low drop because voltage sag during transfers can trip sensitive electronics. Engineers typically design for ≤ 2% drop from genset to main panel.
Best Practices to Reduce Voltage Drop
- ✓Upsize wire one AWG step for any run over 100 ft, then verify with this calculator. The marginal copper cost is far smaller than the lifetime energy loss.
- ✓Prefer copper for long runs unless cost is the dominant constraint. Aluminum requires roughly 1.6× the cross-section to match copper's voltage drop.
- ✓Run parallel conductors on high-amperage feeders (per NEC 310.10(H)) rather than oversizing a single huge cable — termination is cheaper and easier.
- ✓Choose PVC over steel conduit when reactance matters (long three-phase runs) — magnetic conduit substantially raises X.
- ✓Boost voltage where possible — running 240 V instead of 120 V on the same circuit halves the current and quarters the voltage drop in percentage terms.
- ✓Locate the panel centrally in new builds so runs are short and balanced; long radial wiring designs are the #1 cause of avoidable drop.
Common Voltage Drop Mistakes
Sizing for ampacity only
Ampacity tells you the wire won't melt under steady current — it says nothing about whether the load receives enough voltage. Always check both.
Forgetting the round-trip
Distance is one-way; the formula doubles it for DC and single-phase (×2) or applies the √3 factor for three-phase. Skipping this halves your computed drop.
Ignoring temperature
75°C resistance values are NEC's mid-band default. Wire running in a hot attic, near machinery, or fully loaded can sit at 90°C+, with R about 6% higher than nameplate.
Using DC formulas for AC
On long AC runs, ignoring reactance and power factor under-estimates drop by 5–20% on inductive loads. Use the right formula for the phase.
Skipping voltage drop on motor feeders
Motors start at 5–8× their running current. The feeder must hold ≥ 85% of nameplate voltage during start — verify drop using starting current, not just running current.
Trusting nameplate alone
Real installed voltage at the panel can be 5–10 V below nominal. Measure with a meter under load before sizing critical feeders.
Why Voltage Drop Matters
Voltage drop is wasted energy — every percent below the source voltage is current dissipated as heat in the wire rather than delivered to the load. On a 50 A circuit running 24/7, even 3% drop wastes hundreds of dollars per year. On long runs it can cumulatively cost more than the wire itself.
Beyond energy, drop affects performance: lights dim, electronics reset under surge, motors stall, heaters under-perform, and battery chargers run slow. In safety-critical contexts (fire pumps, life-safety branches, generator feeders) it can even prevent equipment from operating during an emergency. Correct sizing protects the equipment, the wallet, and ultimately the people.
Built for electricians, engineers, solar installers, electrical inspectors, and serious DIYers.
Reference values cross-checked against NEC Chapter 9 Tables 8 and 9 (2023 edition) — see our methodology and editorial policy. Educational only — always have an installation reviewed by a licensed electrician and your local inspector.
Frequently Asked Questions
Related Calculators
- Unit ConverterAll-in-one converter for 40+ measurement categories with natural-language input.
- Scientific CalculatorAdvanced trig, log, exponent, root, factorial, and memory functions.
- Percentage CalculatorCalculate % of a number, percentage change, and reverse percentages.
- IP Subnet CalculatorCalculate IPv4 and IPv6 subnets, CIDR ranges, and VLSM allocations.
- Time CalculatorAdd, subtract, convert, and analyze time with duration math and stopwatch timer.
- GDP CalculatorGDP via expenditure and income approaches, per capita, and real vs nominal.